| INPUT |
Input |
Voltage from PT & current from CT. |
PT Ratio |
(1) 110 VAC from PT.
(2) 230 VAC from PT.
(3) 415 VAC from PT. |
CT Ratio |
(1) 0-1 A from CT.
(2) 0-5 A from CT. |
Connections |
(1) 3 phase, 3 wire.
(2) 3 phase, 4 wire. |
Input power range |
Please specify. |
| Operational range(of rating) |
Voltage input |
(1) 10-110% (for externally powered).
(2) 85-110% (for self powered). |
Current input |
0-120%. |
|
|
| OUTPUT |
Output |
4-20 mA DC, linear.
1-5 VDC linear. |
Load on output |
0-500 ohms. |
|
|
| DISPLAY |
Type of display |
7 segment LED display. |
No. of digit |
(a) 3 ½ digit.
(b) 4 ½ digit. |
Size of digit |
100mm (4”) height. |
Display colour |
Red. |
Display range |
Please specify. |
| GENERAL SPECIFICATION |
Isolation |
Galvanic isolation of 1.0 KV is provided between supply & input/output. |
Adjustment |
Zero & span are adjustable by two individual trim-pots. |
Burn out protection |
Down scale. |
Anti-humidity Treatment. |
Acryform conformal coating on PCB. |
Power fuse |
0.25 Amps. |
Wiring |
Screw terminals, suitable for 2.5 Sq.mm. |
| PERFORMANCE |
Accuracy |
±0.5% of full scale, ±1 digit. |
Resolution |
1 LSB. |
Sampling rate |
2 per second. |
Response time |
Less than 2 seconds. |
Line voltage variation effect |
± 0.5% (within ± 10% change). |
Insulation resistance |
200 MΩ at 1000 VDC. |
Insulation strength |
(1) 1KV between earth & primary.
(2) 0.5KV between earth & I/O.
(3) 0.5KV between primary & I/O.
(4) 1KV between input & output. |
| INSTALLATION |
Power Supply |
(A) 110 VAC ± 10%, 50 Hz.
(B) 230 VAC ± 10%, 50 Hz. |
Operating ambient |
|
-Temperature |
0°C to 60°C. |
-Humidity |
5 to 95% RH. |
Mounting |
Flush panel. |
Housing |
Sheet metal. |
Bezel size |
530 (W) x 196 (H) in mm. |
| Weight |
5Kg. |