| INPUT/OUTPUT |
| Input |
|
T/C
|
K / J / N / E / R / S /
|
| Range |
|
| K |
0 to 1240 °C |
| J |
0 to 1000 °C |
| N |
0 to 1300 °C |
| E |
0 to 750 °C |
| R |
0 to 1740°C |
| S |
0 to 1760 °C |
| T |
0 to 400 °C |
| PT - 100 |
0 to 820 °C |
| 4 - 20 mA |
0000 – 1999 |
| 1-5 Volt |
0000 - 1999 |
|
| DISPLAY |
| Type of Display |
7 Segment Display |
| No. of Digits |
4 Digit for Channel No. & 4 Digit for Parameter Value |
| Size of Digits |
12.5 mm (0.5”) Height |
| Display Colour |
Red |
|
| SET POINTS |
| Setpoints |
Programmable Alarm & Trip Set point for each Channel |
| Dead Band |
Programmable from 0 – 254 |
| Setpoints Settings |
Hi for Alarm type
Hi / Lo Programmable for Trip type |
| Output Relays |
4 |
| Control Action |
ON / OFF |
| Grouping of Relays |
Programmable |
| Alarm & Trip LEDs |
Common for both for each Channel |
|
| GENERAL SPECIFICATION |
| Mode of Operation |
| Auto Scan |
All Channel are sequentially scanned at the rate selectable from 1 to 12 sec. |
| Hold Mode |
Any particular channel & its reading can be held indefinitely |
| Skip Facility |
Provided to skip undesired Channel |
| Operation |
Fail safe ( relay energised for normal running ) |
| ACJC |
Inbuilt& Automatic for T/C I/P |
| Calibration |
Through software of individual I/P’s. |
| Sensor Break & Short Circuit Protection |
Indication |
| Accuracy |
± 0.5%, ± 1 Digit |
| Response Time |
WITHIN 3 Sec. |
| Insulation Resistance |
200 MΩ at 1000 VDC |
| Watch Dog Timer |
Both H/W & S/W provided |
| Memory Retention |
EE-PROM (more than 5 years ) |
| Anti-Humidity Treatment |
Acryform conformal coating on PCB |
|
| INSTALLATION |
Power Supply |
a) 110 VAC ±10%, 50Hz
b) 230 VAC ±10 % 50Hz |
Operating Temperature |
0 to 60°C |
Operating Humidity |
5 to 95% |
Storage Temperature |
0°C to 60°C |
Mounting |
Panel Mounted |
Terminals |
Screw terminals suitable for conductors upto 1.5Sq. mm |
Instrument Cabinet |
Plastic Housing |
Bezel Size |
96 x 96 mm |
Cutout Size |
92 x 92 mm |
Depth |
165.5 |