| INPUT/OUTPUT |
| Input |
|
| T/C |
K / J / N / E / R / S / T |
| RTD |
Pt-100
|
| mA |
4 - 20 mA |
| Volt |
1 - 5 Volt |
| Range |
|
| K |
-180 to 1350 °C |
| J |
-120 to 1000 °C |
| N |
0 to 1300 °C |
| E |
-120 to 750 °C |
| S/R |
0 to 1760°C |
| T |
0 to 400 °C |
| Pt - 100 |
-180 to 840 °C |
| 4-20 mA |
–1999 to 9999 |
| 1 - 5 Volt |
–1999 to 9999 |
|
| DISPLAY |
| Type of Display |
7 Segment Display |
| No. of Digits |
3 Digit for Channel No. & 4 Digit for Parameter Value |
| Size of Digits |
12.5 mm (0.5”) Height |
| Display Colour |
Red |
|
| SET POINT |
| Set Points |
Programmable Alarm & Trip Set points for each Channel |
| Dead Band |
Programmable from 0 - 254 |
| Set point settings |
Hi for Alarm type
Hi / Lo Programmable for Trip type |
| Output Relays |
8 |
|
| GENERAL SPECIFICATION |
Mode of Operation |
|
| Auto Scan |
All Channel are sequentially scanned at the rate selectable from 1 to 180 sec. |
| Auto Acknowledge |
For Alarm value, there is Auto reset |
| Hold Mode |
Any particular channel & its reading can be held indefinitely |
| Skip Facility |
Provided to skip undesired Channel |
| Operation |
Fail safe (relay energized for normal running) |
| ACJC |
Inbuilt & Automatic for T/C I/P |
| Calibration |
Through software of individual I/P’s. |
| Sensor Break & Short Circuit Protection |
Indication |
| Accuracy |
± 0.5%, ± 1 Digit |
| Response Time |
WITHIN 3 Sec. |
| Insulation Resistance |
200 MΩ at 1000 VDC |
| Watch Dog Timer |
Both H/W & S/W provided |
| Memory Retention |
EE-PROM (more than 5 |
| Anti Humidity Treatment |
Acryform Conformal coating on PCB. |
| Control Action |
ON / OFF |
| Grouping of Relays |
Programmable |
| Alarm & Trip LED’S |
Common for both for each Channel |
|
| INSTALLATION |
| Power Supply |
90-270 VAC, 50Hz |
| Operating Temerature |
0 to 60°C |
| Mounting |
Panel Mounted |
| Terminals |
Screw terminals suitable for conductors up to 1.5Sq. mm |
| Instrument Cabinet |
Sheet Metal |
| Bezel Size |
288 x 144 mmx50mm |
| Cutout Size |
282 x 138 mmx50mm |
|