Pyrotech Electronics Pvt. Ltd. (Unit - I)

SIGNAL ISOLATOR (QUAD OUTPUT)

MODEL CODES
Model                           CON 408
Type                            

4-Wire

INPUT/OUTPUT

Input    

mA / Resistance / Volt T / C, RTD, Frequenc

Input Impedance for Circuit  

36 W For Current Input

Current Input 0-120%
Output 4-20 mA Quad O/P
Output Ripple Better than ± 0.25% r.m.

Load on Output

0-750 W

GENERAL SPECIFICATION

Isolation        

Optical & Galvanic

Adjustment 

Zero & Span are Adjustable by two individual trim-pots.

Anti-humidity treatment 

Acryform conformal coating on PCB

Wiring  

Screw terminals (M 3)

Accuracy

± 0.25% of Span

Response Time

Within 1 Second

Insulation Strenght

1500V rms.

INSTALLATION

Power Supply (For externally powered)   

(i) 110 VAC ± 10 %, 50 Hz

(ii) 230 VAC ± 10 %, 50 Hz

Power Consumption  

Less than 10 VA

Operating Ambient

 

- Temprature

0-60°C

- Humidity

5-95% RH.

Storage Temperature               

0°C to 70°C

Mounting

Din Rail

Housing  

ABS

Terminals

M3 suitable for conductors upto 2.5 sq. mm.

Size         

112 (H) x 150 (W) x 70 (D) in mm.